YT-02系例電動(dòng)執行器

YT-02系例電動(dòng)執行器

YT-02 series
 
◎Mini volume,exquisite appearance (L104-W70-H90)
                                      
◎Rated torque:20Nm
◎Protection level:IP67
◎Mechanical connecter: ISO5211(F03、F04、F05)
◎Out put bearing:male square12x12,female square 8x8,11x11,14x14
◎High performance brushless motor,it can be used up to 20000 times
※YT series is all for plastic housing: ABS /PC+PET
               YT series is all for die casting aluminium outer case  finished:passivation and plastic spraying
 
 

Product model Rated voltage time Additional function Operating characteristics note
YT-02N
normal on/off actuator
DC12/24V 10S@DC series   Continuous operation
passive contact feedback
feedback asynchronous with arrival
AC24/110/220V 15S@AC series   HTR (anti condensation heater) Discontinuous operation of ED=75%
AC/DC24V 10S KT329(failsafe) Continuous operation
AC/DC95-265V     HTR (anti condensation heater)  
YT-02C
intelligent on/off actuator
DC12V
AC/DC24V
AC/DC95-265V
10S
 KT32(failsafe)
A(output fault signal)
HTR(anti condensing heater)
Continuous operation
Synchronization of feedback signal with actual location
With PUL speed regulation and PWM speed regulation
0.9/1.3 inch OLED LCD screen
Can be achieved: two or three, four position mode
YT-02T
intelligent modulating actuator
DC12V
AC/DC24V
AC/DC95-265V
10S
 KT32(failsafe)
A(out put fault signal)
HTR(anti condensing heater)
Continuous operation
0.9/1.3 inch OLED LCD screen
Control feedback mode:
4-20mA/0-20mA/0-10mA
0-5V/1-5V/0-10V/2-10V
YT-02B
intelligent bus actuator
DC12V
DC24V
AC95-265V(Not recommended) 
10S
 KT32(failsafe)
HTR(anti condensing heater)
Continuous operation
RS485,CANBus2.0 Profibus 
with0.9/1.3寸OLEDscreen
on/off actuator with PUL speed regulation and PWM speed regulation
bus on/off actuator(ON、OFF、B33)
bus modulating actuator,adjustment accuracy5‰
YT-02D  intelligent timer actuator DC12V
AC/DC24V
AC/DC95-265V
10S
KT32(failsafe)
HTR(anti condensing heater)
Continuous operation
with0.9/1.3寸OLEDscreen
have rechargeable battery
can stay more than 60days after power off
Pulse timing mode、moment timing mode
cycle by day,cycle by week
YT-02R
intelligent wireless actuator
DC12V
AC/DC24V
AC/DC95-265V
10S
KT32(fail safe)
HTR(anti condensing heater)
Continuous operation
wireless on/off actuator(ON、OFF)
with0.9/1.3 OLEDscreen
wireless modulating actuator,adjustment accuracy5‰
communicate frequency:433/868/915MHZ
LORA/FSK :  max2.5KM(open land)
ENOCEN: 20-100m

Dimension


Main parts
 
 
  component material
1 actuator  heat resistantABS/die casting aluminium
2 Instruction window TransparentAS
3 screwx4 304
4 manual bearing 304
5 manual bearing oil seal NBR
6 label PVC
7 hex wrench fixed card heat resistantABS/die casting aluminium
8 hex wrench tool steel
9 water proof NiLon
10 upper and lower cover seals NBR

Install the actuator and valve

 


  • Diagram1-1  UPVC plastic ball valve add bracket assembly
  • Diagram1-2  3-piece stainless steel ball valve assembly
  • Diagram1-3 Stainless steel 3-way ball valve assembly
  • Notice: 1.When install the actuator with valve,it’s recommend to use Spring Washer add flat washer to fix Screw and nut.
  • ※2.It’s forbidden to use Anaerobic glue or UV glue,if in need ,please use 704 glue and quick adhesive.
  • ※3.Casing is avoid contacting with organic solvent,such as kerosene, butanone and so on,or the casing
  • will be damaged

Matched valve technical requirements
  • 1.When installing ball valve, the max torque ≤15Nm. If the ball valve is out of operation for a long time, and the torque value of first on or off is the max torque. Or you can choose ball valve with elastic sealing.
  • 2. When installing butterfly valve, the max torque≤13Nm. Because the torque value will increased by 10-20% after installing.
  • 3.When installing direct mount mode valve, the hole deep ≤15mm. It requires cutting if the output shaft is longer than 15mm.
  • 4. Please pay attention to the following items if you install the bracket and coupling by yourself:
  • ※ The intensity of bracket should meet the using requirements: the bracket twisting extent ≤0.2mm in the process of on or off.
  • ※ The parallelism of bracket ≤0.5mm.
  • ※ When processing the shaft hole at both end of the coupling, it is necessary to ensure the accuracy and concentricity. The purpose is to make sure the mechanical hysteresis ≤10°, otherwise it will cause the actuator unable to work.
  • 5. Screw should be installed spring washer、flat washer, and we suggest you daub some glue cement around the screw in case of screw loosening.
  • 6. After installation, user should switch the valve on and off one time with handle device first. Modifying the valve after make sure it works well
     

Work environment
 

  • □ This product can be used indoor and outdoor.
  • □ This product is not explosion proof, do not use them in flammable and explosive environment.
  • □ You need to install protective device for the actuator if it is exposed to the rain or sunshine.
  • □ Please pay attention to the ambient temp.
  • □ When installing, you need to consider the reserved space for wiring and repairing.
  • □ When power on, it is not allowed to dismantle actuator and valve.
  • □ When power on, it is not allowed to do wiring.
  • □ ※Forbid dropped things hit the device and lead to improper operation.
  • □ ※Forbid to step on it which will cause device malfunction or personal accident.
  • □ ※It is forbidden to do wiring project in rainy day or when there is water splash.
  • □ 02 series is forbid to open the case for wiring,or it will damaged the Sealing performance
     

Safety notice
  • □ In order to use the device safely for a long time,please pre-read the manual carefully to ensure correct use.
  • □ Notice item:Please understand the product specification and using method clearly to ensure personal safety or prevent device
  • □ In order to indicate damage and danger,here we classify them as “warning ” and “notice ※ ”.
  • □ Both of contents are very important,which should be obeyed strictly.
  • □ “Warning ”:It will cause death or serious injury if not obeyed.
  • □ “Notice ※ ”:It will cause slight injury or device damage if not obeyed.